Modbus RTU (RS485) connection
The Link supports communication with external installation components via the Modbus RTU protocol. To establish a reliable connection, all devices on the network must "speak the same language" by sharing identical communication settings.
-
Record the serial settings. First, consult the manufacturer's user manual for each external Modbus device and record the following serial communication parameters. These must be consistent across your entire network.
- Baud rate: the speed of communication (e.g. 9600 bps).
- Data bits: the number of data bits in each character (typically 8).
- Parity: the method of error checking (e.g. none, even, odd).
- Stop bits: the bits that signal the end of a character (typically 1).
Same settings on every device
Different settings: not allowed
The Link only has a single RS485 port. If the characteristics of the installation components require to set more than two homogeneous networks, due to different baud rates, then an additional Link is required.
-
Wire the serial network.
In a chain, from device to device
In a star: not allowed
The end nodes in an RS485 network must have a 120 ohm resistor between the A and B or the (+) and (−) terminals.
-
Connect the network to the RS485 port of the Link.
Ensure correct polarity. Connect the positive A/+ terminal to positive A/+ and the negative B/− terminal to negative B/−. Reversing these connections can lead to communication failure or equipment malfunction.